Circutor computer PLUS-TF Series Manual de usuario

Busca en linea o descarga Manual de usuario para Instrumentos de medición Circutor computer PLUS-TF Series. CIRCUTOR computer PLUS-TF Series User Manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir

Indice de contenidos

Pagina 1 - INSTRUCTION MANUAL

1 POWER FACTOR REGULATOR COMPUTER plus TF (Three-phase Measurement - Static Switching) INSTRUCTION MANUAL M98223301-03-09B

Pagina 2 - CONTENTS

10 Construction features: Connection Direct connection terminals for rigid 2.5 mm wire (4,5 mm2) or flexible (AWG 11) Box material V0 self-exting

Pagina 3

11 3 STANDARD CONNECTION DIAGRAMS J. BalcellsJ. Balcells 11-06-2007BATERIA ESTÁTICA CON CPC3i-4RSMANDO TRIFÁSICO O FASE FASE CON RS-485945 XXX ve

Pagina 4

12 L1L2L3NAC SUPPLYCOMAL1LC1G11K11G21K22G12K12G22K23G13K13G23K2Power BlockCPC3i-xRS0V230V400V2G22K22G12K13G23K23G13K11K21G21G11K1AL1COMSHRS+RS-ABCDE

Pagina 5 - Computer plus

13 3.1 Cards and Functions Card A: Com + Measure C + LeakagesCard B: RelaysCard C: P.S. + measure + Alarm relaywww Computer plus TF includes tw

Pagina 6

14 5 Voltage 3 6 Neutral 7 Secondary 1 Current IA 8 Secondary 2 Current IA 9 Secondary 1 Current IB 10 Secondary 2 Current IB 11 Secondary 1 Current

Pagina 7 - CAPACITOR

15 CARD A TERMINALS ALLOCATION FUNCTION 31 A+ Terminal A+ RS-485 (control of capacitors Only TF versions) 32 B- Terminal B- RS-485 (control of capa

Pagina 8 - Types and basic functions:

16 3.3 Connection of current transformers The unit measures the current of the three input phases with three current transformers. The PF equipment

Pagina 9 - 2 TECHNICAL SPECIFICATIONS

17 Fig. 8 .- Connection of the line current transformers

Pagina 10 - 2.1 Dimensions and fixings

18 4 SETTINGS AND START-UP Read the safety instructions in the introduction of this manual. You must respect these conditions to g

Pagina 11 - 945 XXX vers 0.0

19 All connections are inside electric panel. Remember that with the unit connected, the terminals may be hazardous to the touch, an

Pagina 12 - Power Block

2 CONTENTS 1 COMPUTER PLUS TF POWER FACTOR REGULATORS ... 7 2 TECHNICAL S

Pagina 13 - Card B: Relays

20 4.2 Energising the regulator.  The device can be energised once the power supply and measuring cables have been connected.  After energis

Pagina 14

21 5 BASIC INSTRUCTIONS TO BROWSE THE MENUS 5.1 Browsing the menus: Functions of the keys The Computer plus system has four dynamic keys, marked F

Pagina 15

22 Fig. 11.- Default screen in the STOP mode Fig. 12.- Default screen in the RUN mode Fig. 13.- Main Menu Screen All screens will display the me

Pagina 16

23  Set Alarm: (Alarm Setup). Used to adjust the maximum and minimum trip, delay, etc. values.  Alarms: Shows the state of alarms  Harmonics:

Pagina 17

24 6 SUBMENU LAYOUT Each of the basic functions described in the main menu (folders) has a series of options or submenus that allow the configu

Pagina 18 - 4 SETTINGS AND START-UP

25 6.2 Device setup menu In the setup menu you can configure the different options of Computer Plus. This menu is protected by a password. You can

Pagina 19 -  VERY IMPORTANT!

26 6.3 Alarm setup menu The alarm setup menu displays and allows the programming of the alarms of Computer Plus. This menu is protected by a passwo

Pagina 20 - 4.3 Regulator settings

27 6.4 Alarm status menu This menu displays and allows resetting of alarms that have tripped, but it can not be used to change the limits or activ

Pagina 21

28 6.5 Harmonics menu This menu displays 32 harmonics from the different voltages and currents measured by Computer plus. HARMONICS MENUScreens Har

Pagina 22

29 6.6 Test menu The Test menu can be used to enter the device's manual mode. The options in this menu have been designed to

Pagina 23

3 7.3 MANUAL SETUP ...

Pagina 24 - 6.1 Measure menu

30 Fig.20.- Password request 7.2 "Plug & Play" Setting One of the most important features of Computer plus when compared to oth

Pagina 25 - 6.2 Device setup menu

31 Fig. 21.- Main menu Fig.22.- Setup menu  Select the option and press OK . The screen shown on Fig. 23 will be displayed.  Press Edit a

Pagina 26 - 6.3 Alarm setup menu

32 Fig.25.- Programming capacitor power Fig.26.- Programming capacitor power  On the screen shown on Fig.25, use the arrow to change the digit

Pagina 27 - 6.4 Alarm status menu

33 7.2.2 Plug&Play Step 2  Nominal voltage of capacitors and steps configuration: The second Plug&Play step involves the sel

Pagina 28 - 6.5 Harmonics menu

34 7.2.3 Plug & Play Step 3  After configuring the power and capacitor steps configuration, the automatic setting can be launched. To do so,

Pagina 29 - 7.1 Password

35 Fig.37.- Plug&Play. Phase allocation information Fig.38.- Plug&Play. Phase allocation information Fig.39.- Plug&Play. Secondary s

Pagina 30

36  If there is an error message at the end of the automatic adjustment process, carry out the process again and if the error persists, the system

Pagina 31

37 7.3.1 General information about the Setup menu  To edit a field, follow the procedure described in section 5.4.  The screen displayed on Fig

Pagina 32

38  You can browse any parameter to see how it is programmed. However, when you attempt to edit a field, a screen will ask for the password (Fig.

Pagina 33 - OK and

39 NOTE: Any power rating can be used on each step. However, these are usually established in ascending order, respecting the 1:1:1:1; 1:2:2:2 or 1:

Pagina 34 - OK . The screen shown on

4 11 HARMONICS DISPLAY ...

Pagina 35

40  To edit the information on the screen shown on Fig.47, press the Edit option and the screen shown on Fig.48 will be displayed. Use the arrow t

Pagina 36 - 7.3 MANUAL Setup

41 Fig. 50.- Transformer Ratio Fig. 51.- Edit Transformer Ratio  Press Edit and the screen shown on Fig.52 will be displayed. To edi

Pagina 37

42 Fig. 54.- Transformer Ratio Menu Fig. 55.- Edit Transformer Ratio Menu  Press Edit to adjust the desired value. To edit a field, follow the

Pagina 38

43  Select the Compensation (Fig.58) option and press OK The screen on Fig.59 will be displayed.  Press Edit to adjust the desired parameter va

Pagina 39

44 Fig. 60.- Date and Time Adjustment Menu Fig. 61.- Edit Date and Time Adjustment Menu 7.3.11 Adjusting the Display  Open the setup menu by f

Pagina 40

45 7.3.12 Adjusting Communication Settings This option is used to adjust the communications parameters of channel COM1, in order to integrate

Pagina 41

46 Fig. 66.- Clear / Update Menu Fig. 67.- Edit Clear / Update Menu  The following parameters can be configured: Max… Deletes the maximum and m

Pagina 42

47 8.2 Measurable parameters  The options available and measurable parameters are summarised on table 8.1.  Each option can be selected with tw

Pagina 43

48 Fig. 70.-Power, cos , FPIII Fig.71.- Status III Fig. 72.- Status Fig.73.- cos  Fig. 74.- PF Fig.75.- V phase-phase

Pagina 44

49 Fig. 76.- V phase-neutral Fig.77.- I Line Fig. 78.- I Neutral Fig.79.- I Cond (Only in TF-CDI) Fig. 80.- I leak, I N Cond Fig.81.- Power

Pagina 45

5 INTRODUCTION CIRCUTOR S.A. would like to thank you for showing your trust by choosing one of our Computer plus series regulators These units are

Pagina 46

50 Fig. 82.- kW Fig.83.- kvar Fig. 84.- kVA Fig.85.- Temperature Fig. 86.- Imported Energy III Fig.87.- Exported Energy III

Pagina 47

51  Some parameters record the maximum or minimum values and indicate the date and time when they occur. The parameter screens show the Max or Min

Pagina 48

52 9.2 Alarm setup options  Table 9.1 shows a summary of each alarm option that can be configured and table 9.2 defines each option available.

Pagina 49

53 Common alarm legends HI……... High alarm limit value LO………Low alarm limit value DelayT… Delay time before the activation of the alarm (in second

Pagina 50

54 Fig.94.- Configuring standard alarm screens Fig.95.- Editing standard alarm screens 9.4 Special Alarm scenarios Some alarms have certai

Pagina 51 - 9 ALARM SETUP

55 9.4.4 Earth Leakage Transformer Fault Alarm (only in TF-CDI) This alarm can not be programmed. Computer plus is configured by default so that wh

Pagina 52 - 9.2 Alarm setup options

56 10.1 Opening the alarm display menu  To open the alarm display menu, go to the main menu (Fig.98). Use the arrows to select the folder

Pagina 53 - 9.3 Configuring each alarm

57 Options Comments Meaning Global Enable Shows the global alarm enable status. The following can be displayed: ON… Global enable activated and s

Pagina 54 - 9.4 Special Alarm scenarios

58 HI High value that triggered the alarm. No value will be displayed when the alarm has not been triggered due to the HI limit. LO Low value tha

Pagina 55

59 10.2.2 I leak alarm As mentioned in section 9.4.1, Computer plus will treat this alarm as a special case. This alarm can be used to disconnect

Pagina 56

6  Maintenance must be performed taking the necessary precautions to avoid electrocution and electric shock. Before any intervention, we recommend

Pagina 57

60 Fig. 106.- Current fault alarm screen 11 HARMONICS DISPLAY Computer plus also includes an option to display voltage and current harmonics. It

Pagina 58

61  The options will be selected from the list shown on Fig. 108 with the dynamic keys . Press OK when the option selected appears on the revers

Pagina 59

62  The numerical display screens show the Grap dynamic key. Press the key to display the harmonics in a bar graph (Fig.110) and use the keys to

Pagina 60 - 11 HARMONICS DISPLAY

63 12.1 Opening the Test menu  To open the test menu, go to the main menu (Fig.113). Use the arrows to select the folder and press OK. A li

Pagina 61

64  Use the keys to connect or disconnect the capacitor steps sequentially. While doing so, check how the cos φ is changed when entering or rem

Pagina 62 - 12 TEST

65 Fig. 117.- Capacitor Test Selection Fig. 118.- Disconnection of capacitors Fig. 119.- Capacitor Test Menu Fig. 120.- Capacitor Test Menu  Pr

Pagina 63 -  and resonance test

66 Table 13-1.- Connection of CPC3i to Computer plus  The connection diagrams of the complete unit are shown on Fig. 2 and 3.  Each CPC3i card o

Pagina 64

67 Slave Nr 1 byteFunct1 byte1st bit addr.2 bytesNr of bits2 bytesNr Oct1 byteDataCRC2 bytes00 0F 00 - 64 00 - 40 08 DD0 A DD7 XX - XXBroad, to allF

Pagina 65

68 14 INTEGRATION OF COMPUTER PLUS IN THE SCADA POWER STUDIO PROGRAM Computer plus types TF-C and TF-CDI have an additional COM1 communications cha

Pagina 66 - 13.1 MODBUS Control frame

69 17 TECHNICAL SERVICE If you have any doubts about the operation of the unit or any faults, contact our technical service at

Pagina 67

7 1 COMPUTER PLUS TF POWER FACTOR REGULATORS The regulators in the Computer plus series are power factor regulators that incorporate the latest adva

Pagina 68 - 16 MAINTENANCE

8 Types and basic functions: TYPE VOLTAGE (Vac) OUTPUT MEASUREMENT OTHER FUNCTIONS Computer plusTF-C 110-480 16 static outputs Three-phase Basic typ

Pagina 69

9 2 TECHNICAL SPECIFICATIONS Auxiliary power supply: 110 to 480 Vac (50…60 Hz) (± 10%) Consumption of the unit:  6.6 VA / 230 V ÷ 19 VA / 400 V ÷

Modelos relacionados computer PLUS-T Series

Comentarios a estos manuales

Sin comentarios