Circutor CVM-B Series Manual de usuario Pagina 311

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 320
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 310
10.3.- DIGITAL ANALOGUE INPUTS/OUTPUTS
General features
Maximum power of the module 3W
Analogue outputs
Quantity 8
Maximum internal voltage 12 V
Linearity <1%
DAC resolution 4096 dots
Analogue outputs in current mode
Nominal output range 0-20 mA or 4-20 mA (Programmable)
Maximum load resistor 300
Analogue outputs in voltage mode
Nominal output range 0-10 V
Minimum load resistor 5000
Analogue inputs
Quantity 4
Type of measurement Current
Nominal input range 0-20 mA or 4-20 mA (Programmable)
Accuracy <1%
Input impedance 150
Maximum acceptable input current
22 mA
Environmental features
Operating temperature -10ºC ... +50ºC
Storage temperature -20ºC ... +80ºC
Relative humidity (without condensation) 5 ... 95%
Maximum altitude 2000 m
Protection degree
IP30
Mechanical features
Dimensions (mm) Figure 215 and Figure 216
Weight 80 g
Enclosure V0 self-extinguishing plastic
Assembly Panel
Standards
Safety requirements for electrical equipment for measurement, control
and laboratory use
IEC 61010: 2010
Electromagnetic compatibility (CEM). Part 6-2: Generic standards. Immu-
nity for industrial environments.
UNE-EN 6100-6-2:2006
Electromagnetic compatibility (CEM). Part 6-4: Generic standards. Emis-
sions standard for industrial environments.
UNE-EN 6100-6-4:2007
Coordination of the insulation of units installed in low voltage systems
(networks)
IEC 664: 2007
Information technology equipment. Radio disturbance characteristics.
Limits and methods of measurement.
UNE-EN 55022
311
Instruction Manual
CVM-B100 - CVM-B150
Vista de pagina 310
1 2 ... 306 307 308 309 310 311 312 313 314 315 316 ... 319 320