------ Absorption filter ------ User Manual, M98206701-03-07A ------ Page 5 of 11------
3.- TYPES ACCORDING TO FILTER COMPOSITION
The types of filters depend on three main parameters:
Voltage and basic frequency of system
Step number of filter
3.- TECHNICAL FEATURES
The technical features stated in this manual are for the FAR-Q hybrid banks. However
there may be variations depending on the operating and protection systems.
3.1.- Main Technical Features
Table 3.- Technical features
Standard voltage ........…. 400V and 480 V (1)
Frequency....................... 50 Hz or 60 Hz
Ambient temperature...… -10ºC to +45ºC
General filter switch See table 4
Protection devices (each step) Fuses. Thermostat on L (overload disconnection)
Filter cabinet:
Cabinet protection devices
Filter cabinet
Painted Fe sheet
IP22
Grille: IP21
Standards IEC-61642, EN-60439, IEC-664, EN-60831, EN-60289
(1) Other voltages on request
Cabinets (See figures 3, 4 and 5)
Operation cabinet Sheet metallic, epoxy paint, IP 31
L and C cabinet Ventilation grille, epoxy paint, IP 21
Types and weight (See catalogue)
Dimensions
FA5 Type
2 x FA5 Type
FR6 Type
2 x FR6 Type
(See figures 3, 4 and 5)
One cabinet: L =980 mm, W= 520 mm, H= 2000 mm
Two cabinets: L =980 mm, W= 520 mm, H= 2000 mm
One cabinet: L =1100 mm, W= 800 mm, H= 1850 mm
Two cabinets: L =1100 mm, W= 800 mm, H= 1850 mm