- Check that the steps connect and disconnect properly
- Check that there is no consumption in any phase with the step disconnected. If there is
consumption this means that some of the thyristors are defective.
- Check the consumption of the different steps, in each phase. The normal values are shown in
Table7-4
Table 7-4.- Nominal consumption of the LC steps of an FRE or FRES filter
POWER
CURRENT
230V
400V
I
n
I
n
2.5 kvar
6.28 A
3.6 A
5 kvar
12.56 A
7.2 A
7.5 kvar
18.85 A
10.8 A
10 kvar
25.12 A
14.4 A
12.5 kvar
31.41 A
18 A
15 kvar
37.7 A
21.6 A
20 kvar
50.24 A
28.8 A
25 kvar
62.82 A
36 A
30 kvar
75.4 A
43.2 A
40 kvar
100.48 A
57.6 A
50 kvar
125.64 A
72 A
60 kvar
150.8 A
86.4 A
70 kvar
175.92 A
101.1 A
80 kvar
200.96 A
115 A
- Check the voltage on all of the reactor's windings (input - output of the same winding, not
between phases). The voltage depends on the filter's p% factor (see label on the equipment), in
accordance with the following formula:
%)p100(
%p.577,0
VV
)phasephase(MAINSL
=
For example, in the case of the 400V grid and p%=7, V
L
=17.38V. For the 400V grid and p%=14,
V
L
=37.57V. For other line voltages, the V
L
value is proportional to the line voltage.
NOTES:
When the consumption of the steps is 25% less than that stated in Table7-4 and the voltage is within
the tolerance limits, this is a sign of degradation in the capacitors. These must be replaced with a
suitable spare part if these symptoms are detected in a step.
When the consumption of the steps is 10% more than the values stated in Table7-4, this can be
caused by the presence of resonances. If this is detected, measure the grid's voltage THD (it must be
under 5%) or check the filter's tuning frequency.
If the voltage drop in a reactor deviates from the values stated in this section, check the reactor. This
phenomenon can be caused by the presence of a resonance.
7.3.3 PF regulator checkings.
Refer to the manual of the specific regulator used in the capacitor bank. This
manual is always supplied with the capacitor bank.
Make sure that there are no damaged segments on the display (abnormal brightness).
Make sure that regulator's keyboard is working properly:
- Enter Setup and check the adjusted values
- Force the manual connection and disconnection of a step.
7.4 Environmental Conditions:
Check that the maximum environmental conditions listed in section 4.3 are observed