------ LCL filters: Instructions Manual ----- Page 4
4
WARNING!!!: Due to the LCL filter performance mode, it is quite likely to find elevate harmonic
distortion levels of voltage at the input of the speed drive (downstream to the filter output reactor (L2)).
This voltage distortion should cause no malfunction of the speed drive to be filtered, but it is very much
recommendable, in case that this power drive is taken the auxiliary voltage supply of the control
system from the input of the drive, to take this auxiliary supply from the LCL input, that is, upstream to
the filter input reactor (L1).
Fig. 2.a. Mains supply without LCL filter
Fig. 2.b. Mains supply without LCL filter
4 TECHNICAL CHARACTERISTICS
4.1 General.
Standard voltage (phase to phase)
400V (Others on request)
Frequency
50Hz for types LCL-35-xx or 60 Hz for types LCL-36-xx
Rated load current
See table of types
Rated filtering current
See table of types
Parallel filter protection
Fuses NH or NZ type depending on size
Residual THD
Aprox. 8%
Voltage drop at rated current
< 2%
Standards
EN 60439, EN 60831 ; EN-50081-1, EN-50081-2 , class A
Ambient temperature
Ambient : 40ºC
Relative Humidity
80%
4.2 Reactors
High permeability metal sheet / Aluminium
2kV
<3%
1,6 of rated current
60ºC
<110ºC
90 ºC
25%
20%
2 I
rated
4.3 Capacitors
Polypropylene Self-healing