Circutor MDC-20 Manual de usuario Pagina 53

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 58
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 52
MDC-20
User Manual Page 53 of 58
The variables for the maximum demand controller are shown in the image.
Fig.8-49 . Variables of the MD controller
Set point (kWh): Consumption value that cannot be exceeded and depends on the
maximum power configured.
Real (kWh): This is the total consumption for the period in progress calculated according
to the configured energy variable.
Trend (kWh): Estimated consumption value at the end of the period based on current
(real) consumption.
Power (kW): Power value calculated by the unit according to the energy measured in a
period.
Synchrony: This option only appears if external synchronisation has been activated in
the editor. Indicates the date and time when it was activated.
Reset: Moments when the demand control unit has been restarted.
The load variables that can be represented as graphics are
Fig.8-50 . Variables for graphic representation
Available: Value of variable configured for enabling the load. Indicate whether it is
available or not for the power control. Normally its value changes between 1 and 0;
otherwise it must change between a positive and negative value.
Vista de pagina 52
1 2 ... 48 49 50 51 52 53 54 55 56 57 58

Comentarios a estos manuales

Sin comentarios