----- Relay Station CBS-8 -------- --- Page No. 26
Time between reclosures.
) Value between 1 and 900 seconds
Type of time between reclosures.
Applying time between reclosures creates two reclosure modes:
- Normal: Time between two consecutive reclosures is equal to the value preset
by the user in the previous parameter.
- Exponential: For each reclosure the reclosing time is: trec
n+1
= trec
·2
n
, where
n is the number of reclosures up to now and trec is the reclosing time selected
by the user.
Normal Exponential