Circutor computer SMART III-Fast Series Manual de usuario Pagina 97

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 108
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 96
Ifthevalueenteredislowerthantheminimumvalueorhigherthanthemaximumvalue,
thebacklightofthedisplayashesandthevalueenteredisreplacedwiththeminimumor
maximumvalue,orwiththelastvaluevalidated�
Pressthe keytoaccessthenextprogrammingstep�
Ifnokeysarepressedfor5minutes,theunitswitchestothesimulationscreen,5�27�-
SIMULATION SCREEN
5�23�-CURRENTxITHDALARM
Inthispointthethresholdsabovewhichthealarm
forthepercentageofthevalueofthecurrentx
ITHD(E09)isactivatedcanbeconfigured�
Thealarmmustbeenabled(5�19�- ENABLING
ALARMS”
Theprogrammedvaluesareusefulforthe3
phaseswhichtheunitmeasures�
Pressthe
keytoentereditingmode�Itis
identifiedbythe symbolandtheblinkingof
thedigitstobemodified�
Thevaluetobeprogrammedinthisalarmcorrespondsdirectlytothevalueofthetotal
harmoniccurrenttobeconsideredasthesetpoint�For example: If you want to program a Lo
setpoint value when exceeding a harmonic current of 200 A measured by the regulator, program
00200 directly in this section.
Theparameterstobeconfiguredare:
TheLo value: whentheunitexceedsthisvaluefor30minutes,alarmE09 is
triggered,andifalarmE11 is enabled, the SMART III FASTunitentersNo Connection
statusandactivates alarmE11
TheHI value: iftheunitexceedsthisvaluefor30seconds,alarmE09istriggered,
andifalarmE12isenabled,theSMART III FASTunitenterstheDisconnection status
andactivates alarmE12
IftheunitfallsbackundertheLo valuefor10minutes,itdeactivatesthealarmsandreturns
tothenormaloperatingstatus�
IntheNo Connectionstatus,theunitdoesnotconnectthestages,butalsodoesnot
disconnectthemiftheoperationrequiresit�
IntheDisconnectionstatus,itdisconnectsallthestagesanddoesnotallowthemtoconnect�
The keyincreasesthedigitvalue�
97
Instruction Manual
Computer SMART III FAST
Vista de pagina 96
1 2 ... 92 93 94 95 96 97 98 99 100 101 102 ... 107 108

Comentarios a estos manuales

Sin comentarios