Circutor OPTIM-FR Series Manual de usuario Pagina 15

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 19
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 14
Instruction Manual 13
Table 7-2.- Tightening torques of the cables to contact terminals
MODEL
Auxiliary (Nm)
POWER (Nm)
GMC-12 1.3 1.6
GMC-18 1.3 2.2
GMC-32 1.3 2.9
GMC-40 1.3 2.9
GMC-50 1.3 4.5
GMC-65 1.3 4.5
GMC-75 1.3 4.5
GMC-85 1.3 4.5
GMC-150 1.3 9
Table 7-3.- Tightening torques of the cables to reactor terminals.
Reactor Connection Terminal (Nm)
R-5-400 Terminal 1.83
R-10-400 Terminal 1.83
R-15-400 Terminal 1.83
RB-20-400 Flat strip 6.2
RB-25-400 Flat strip 6.2
RB-30-400 Flat strip 15.2
RB-40-400 Flat strip 15.2
RB-50-400 Flat strip 30
RB-60-400 Flat strip 30
RB-80-400 Flat strip 30
7.2.3 Key points for inspecting contactors.
Check that the plastic parts are not blackened and do not show signs of burning or hardening.
Check that the head is properly inserted
Check the tightness of cables and terminals, as shown in table 7-2
The terminals must be clean.
If the filter bank includes RD discharge resistances, check they are in good condition (that they
are not open or show signs of burning).
Fig. 7-1 .-
Connection of the discharge resistances
Cleaning the contactors: In dirty environments (dust, sawdust, metal trimmings, etc).
Periodically vacuum the dust and solid remains. There is no estimated time frame for cleaning,
it depends on the amount of dirt that penetrates the filter bank's cabinet.