Instruction Manual 4
Fig. 3-2 .-Unloading with a Forklift
3.3 Storage
The following storage recommendations should be followed for capacitor banks with detuned
filters:
- Avoid placing it on uneven surfaces.
- Do not store in outdoor areas, humid areas or areas exposed to the splashing of water.
- Avoid hot spots (maximum environmental temperature: 45 ºC)
- Avoid saline and corrosive environments.
- Avoid storing the equipment in areas where a lot of dust is generated or where the risk of
chemical or other types of contamination is present.
- Do not place any weight on top of the equipment cabinets.
4
TECHNICAL FEATURES
4.1 Label with the equipment's features
The label with the equipment's features is located inside it, generally next to the PF regulator (refer
to Fig. 4-1). The filter bank includes the p% information, which states the filter's tuning factor. This
information is important to establish the filter's resonance frequency.
Ref.
Cod.
Nr Serie
Q
N
(U
max
)
p% filtro
Norma/Prot
U
N
/U
max
/f
N
I
max
U
aux
/ f
N
Temp
I
cc
FR8-600-440
R36625
3094701005
600 kvar
50 + 50 + 5x100 kvar
7%
EN-61921, EN-61642 / IP21
3x400 V/440 V/50 Hz
750 A
230 V/50Hz
-25 / +45 ºC
35 kA
Made in UE / Spain
Type
Code
Serial Nr
Reactive Power at Umax
Nr of Steps
p% overvoltage factor, U
L
/U
C
in %
Standards / Protection degree
Rated & Maximun voltage / Rated frequency
Maximum current
Auxiliary control voltage (1)
Range of allowable temperature inside the cabinet
Default value. See particular values in the label
80 mm
100 mm
Fig. 4-1.- Label showing the main characteristics
4.2 Electrical features
- Operating voltage and nominal frequency: U
n
/ f , listed on the label
- Design voltage: U
n
+ 10% (440 V for 400V equipment)
- Nominal power and distribution of steps: Q
n
and composition, (see label)
- Overvoltage factor, p% Standard 7% ,
Others 14%, 8.2% and 5.67% (see label)
- Total loss: Standard 3.5 to 4 W/kvar
- Residual discharge voltage: 75 V after 3 minutes
- Overload capacity: 1,3 . I
n
in all items
- Auxiliary control voltage: U
aux
, listed on the label.
NOTE: In general, use a 1.5 mm
2
cable to supply external power.
If “Internal” , is marked, the equipment does not require external power.