Table 7-4.- Nominal consumption of the capacitors, according to the power
Power
CURRENT
230 V
400 V
In
In
2.5 kvar
6.28 A
3.6 A
5 kvar
12.56 A
7.2 A
7.5 kvar
18.85 A
10.8 A
10 kvar
25.12 A
14.4 A
12.5 kvar
31.41 A
18 A
15 kvar
37.7 A
21.6 A
20 kvar
50.24 A
28.8 A
25 kvar
62.82 A
36 A
30 kvar
75.4 A
43.2 A
40 kvar
100.48 A
57.6 A
50 kvar
125.64 A
72 A
60 kvar
150.8 A
86.4 A
70 kvar
175.92 A
101.1 A
80 kvar
200.96 A
115 A
NOTE: If the consumption is below ±25%, and the voltage is normal, this is usually a symptom of
degradation of the capacitors. In case this is detected in a capacitor, it should be replaced with
another capacitor.
7.3.3 Regulator Checks.
Refer to the manual of the specific regulator used in the battery. This manual is
always supplied with the bank.
Check that there are no faulty segments on the display.
Check that the keyboard is operating properly:
- Enter Setup and check the adjusted values
- Force the manual connection and disconnection of a step.
7.4 Environmental Conditions:
Check that the maximum environmental conditions listed in section 4.3 are observed