44
Bit 15 Break of the supply
Switching on/off the unit highlight4038
unit
w/r 0, 1
Value
0 Highlight swiched off
1 Highlight switched on
Description
Reserved...
...
... ...
Meter status. Describes the current state of the
meter. Successive bits present the given event. The
bit set up on 1 means, that the event took place.
Events can be only erased.
4048 Status1 w/r 0...65535
Device address. The write of the value 0 causes the
interface switching off.
4033
Addr
w/r 0...247
Update transmission parameters. Causes the
application of introduced RS-485 interface settings.
4034
sAvE
w/r 0...1
Write of standard parameters4035
SEt
w/r 0...1
Value
0 without changes
1 Setup of standard parameters
Description
Password for parameters
4036
SEc
w/r 0...6000
Value
0 without password
... Entry in parameters preceded by a
request about the password
Description
Current time4037
hour
w/r 0...2359
This parameter occurs in the ggmm format, where:
gg - means hours,
mm – means minutes.
The introduction of a wrong hour will cause the
setting 23, however the introduction of wrong
minutes will generate the setting of the value 59.
Transmission mode4032
prot
w/r 0...3
Value
0 RTU 8N2
1 RTU 8E1
2 RTU 8O1
3 RTU 8N1
Description
2 19200 bit/s
3 38400 bit/s
4 57600 bit/s
5 115200 bit/s