CDP
Instruction Manual 73
Parameter
(8)
Address
Version
2AF8
(8)
These parameters only accept the read function.
Parameter
Address
Status of relays 1, 2 and 3
BB8
This parameter lets you read and modify the status of the relays
(9)
:
Parameter
Address
(10)
Valid data margin
Relay 1
Bit 0
0: relay deactivated 1: relay activated
Relay 2
Bit 1
0: relay deactivated 1: relay activated
Relay 3
Bit 2
0: relay deactivated 1: relay activated
(9)
The status of the relays can only be modified when non-critical load management is in
manual mode.
(10)
Higher bits (bit 3, 4, etc.) must be 0 in the write function.
Parameter Address Valid data margin
Status of relay 4
(reverse current relay)
1
0: relay disabled
1: relay activated
Parameter
(11)
Address
Injection Margin
E8
(11)
To save in the memory the change in this parameter through Modbus, you
need to restart the unit.
Parameter
Address
Activates remote control
E6
Allowed injection
E7